Product Details:
Minimum Order Quantity | 01 Number |
Usage/Application | Provide Supply Back-up for trip Coil,Protection Relay,Indication,& other Load in HT Panels |
Phase | Single Phase |
Brand | Gogate |
Material | Electronic |
IP Rating | IP20 |
Automation Grade | Automatic |
Frequency | 50hz |
Size | (W X H X D) 280 X 135 X 175 |
Color | Black |
Battery Backed Power Pack
Input:- 230V AC OR 110V AC OR Both
Out Put:- 24/30/48/110/220 V DC
Countinuous Load : 100VA
Impulse Load: 450 VA for 240 msec
Back Up: 15-20 Mints (Maximum 10 trip attempts)
Out Put Variation: + or - 2%
No Load VA Burden during charging: Less Than 70 VA
LED Indication:- Input High, charger on, Battery low, Battery Mode, Over Load, Out Put on.
High Voltage Isolation: 2KV For 1 Min
Cold Start : Yes (Push button)
Over Voltage Protection: Yes
Spare Fuses: Yes
Dimension (W X H X D): 280 X 135 X 175
Designed With Referring following standards
1. IEC 60947-1 HV dielectric test for 2KV
2. IEC 61000-4-5 Surge test 4KV
3. IEC 61000-4-2 ESD direct contact 8KV, through air 15KV
4. IP 20 Ingress Protection Rating